Appearance | Applicable fluid 2 The applicable fluid is a liquid that do not erode the liquid contact part materials (such as water, glycol solution, and oil). | Rated pressure range | Control output | Communication method | IO-Link baud rate | Order code |
---|---|---|---|---|---|---|
![]() | Liquid and gas | -0.1 to 1 MPa | PNP | IO-Link Analog | COM2 (38.4 kbps) | E8PC-010D-E |
COM3 (230.4 kbps) | E8PC-010T-E | |||||
NPN | Analog | – | E8PC-010-E | |||
Liquid | 0 to 10 MPa | PNP | IO-Link Analog | COM2 (38.4 kbps) | E8PC-100D-E | |
COM3 (230.4 kbps) | E8PC-100T-E | |||||
NPN | Analog | – | E8PC-100-E | |||
0 to 40 MPa | PNP | IO-Link Analog | COM2 (38.4 kbps) | E8PC-400D-E | ||
COM3 (230.4 kbps) | E8PC-400T-E | |||||
NPN | Analog | – | E8PC-400-E |
Please contact your OMRON sales representative regarding the IO-Link setup file (IODD file).
It must be selected from the adapters below.
Appearance | Type | Nominal diameter of thread 2 The nominal diameter of the thread is the size of the part shown below on the adapter. ![]() | Thread type | Materials | Order code | |
---|---|---|---|---|---|---|
Nominal diameter A | Nominal diameter B | |||||
![]() | R1/8 male | 6 A | 1/8" | R (taper thread) | SUS304 | E8PC-YA-A18 |
![]() | R1/4 male | 8 A | 1/4" | R (taper thread) | SUS304 | E8PC-YA-A14 |
![]() | R3/8 male | 10 A | 3/8" | R (taper thread) | SUS304 | E8PC-YA-A38 |
![]() | G1/4 female | 8 A | 1/4" | G (parallel thread) | SUS304 | E8PC-YA-B14N |
![]() | NPT1/8 male | 6 A | 1/8" | NPT (taper thread) | SUS304 | E8PC-YA-C18 |
![]() | NPT1/2 male | 8 A | 1/4" | NPT (taper thread) | SUS304 | E8PC-YA-C14 |
A Cable is not provided with the Sensor. It must be ordered separately.
Type | Appearance | Cable | Order code |
---|---|---|---|
Socket on one cable end |
| 2 m | XS5F-D421-D80-F |
5 m | XS5F-D421-G80-F | ||
L-shaped![]() | 2 m | XS5F-D422-D80-F | |
5 m | XS5F-D422-G80-F | ||
Socket and plug on cable ends 2 Straight type/L-shape type combinations are also available. | Straight/straight![]() | 2 m | XS5W-D421-D81-F |
5 m | XS5W-D421-G81-F | ||
L-shaped/l-shaped![]() | 2 m | XS5W-D422-D81-F | |
5 m | XS5W-D422-G81-F |
Refer to Sensor I/O Connector/Sensor Controller on your OMRON website for details.
If the excessive pulsation or surge voltage is expected, use a throttle. Install it inside the adapter and use.
Appearance | Type | Material | Order code | Installation method |
---|---|---|---|---|
![]() | For a male adapter | SUS304 | E8PC-YS | ![]() |
![]() | For a female adapter | SUS304 | E8PC-YS-N |
Appearance | Type | Order code |
---|---|---|
![]() | For E8PC-010 | E8PC-YL-1 2 Provided with the sensor. |
![]() | For E8PC-100 | E8PC-YL-2 2 Provided with the sensor. |
![]() | Female for adapter G1/4 | E8PC-YL-3 |
Model | PNP(COM2) | E8PC-010D-E | E8PC-100D-E | E8PC-400D-E |
---|---|---|---|---|
PNP(COM3) | E8PC-010T-E | E8PC-100T-E | E8PC-400T-E | |
NPN | E8PC-010-E | E8PC-100-E | E8PC-400-E | |
Pressure monitoring 2 The pressure precision is defined based on the values measured in the ordinary temperature environment (approx. 23°C) using water at the ordinary temperature (approx. 23°C). | Rated pressure range | –0.1 to 1 MPa | 0 to 10 MPa | 0 to 40 MPa |
Display range | –0.20 to 1.10 MPa | –0.10 to 11.00 MPa | –0.10 to 44.00 MPa | |
Withstand pressure 2 Even instantaneous pressure fluctuation such as water hammer must be within the withstand pressure. If instantaneous pressure fluctuation is expected, use the throttle included in the package. | 4 MPa | 30 MPa | 50 MPa | |
Burst pressure | 8 MPa | 60 MPa | 80 MPa | |
Display resolution | 0.001 MPa | 0.01 MPa | 0.01 MPa | |
Applicable fluid temperature 2 If the pipe temperature exceeds 70°C, do not contact any cables with the pipe. | –20 to +100°C (no icing or condensation) | |||
Pressure response time 2 The maximum actual response time has error of 1 ms when the set response time is 3 to 10 ms, 5 ms when it is 11 to 100 ms, and +5% when it is 101 ms or more. | Control output: Select 3 to 6000 ms Analog output: Set value + 2 ms (90% response) | |||
Pressure monitoring precision | ±1.0% of F.S. or less | |||
Pressure repeatability 2 The pressure repeatability is the error of the detection point when pressure is applied repeatedly in the ordinary temperature environment (approx. 23°C) using water at the ordinary temperature (approx. 23°C) in the rated pressure range. | ±0.3% of F.S. or less | |||
Ambient temperature characteristics 2 The ambient temperature characteristics are prescribed based on the value measured using oil as applying a pressure value of 50% of the maximum rated pressure. | ±0.6% of F.S./10°C | |||
Hysteresis | Variable | |||
Pressure type | Gauge pressure | |||
Temperature monitoring 2 The temperature monitoring precision is prescribed based on the value measured using water. Temperature measurements are affected by both of the temperatures, the medium and the piping. Temperature measuring elements are installed on the back surface of the piezoelectric element (inside the product) and used to measure the temperature. It might take long for the measured value to get stable according to the heat transmission speed. | Temperature monitoring rated range | –20 to 100°C | ||
Temperature monitoring precision | ±4°C | |||
Temperature repeatability | ±1°C | |||
Control output judgment (selectable) | Standard mode | Judge if the measured value is the threshold value or more (or less). | ||
Window mode | Judge if the measured value is within the upper and lower limits. | |||
Compatible fluid | Gas and fluid not corroding the material of the wetted part (such as water, glycol solution, and oil) | |||
Display method | Numerical value indication: 4-digit 7-segment white LED with inverting function Status indicator: Normal operation (green), status indication (orange), and error (red) The content of status indication is selectable. Output indicator: OUT1 operation (orange), OUT2 operation (orange) Unit indication: E8PC- E8PC- IO-Link indicator: Lighting when communications are in progress (green) | |||
Delay setting | 1 to 9999 ms (Select a function from invalid, ON delay, OFF delay, and one-shot.) | |||
Connection method | M12, 4-pole connector type | |||
Connecting diameter | G3/4 male (Use the optional adapter to convert the diameter) Connection strength 20 N·m | |||
Output ch1 (selectable) | Control output | Pressure control output (N.O./N.C.) E8PC- E8PC- 30 VDC or less, Class 2, max. 100 mA, residual voltage 1 V or less | ||
Output ch2 (selectable) | Control output | Pressure control output (N.O./N.C.) / temperature control output (N.O./N.C.) E8PC- E8PC- 30 VDC or less, Class 2, 100 mA max., residual voltage 1 V or less | ||
Analog current output 2 Do not connect analog current output with the master unit of IO-Link. Otherwise, the unit might fail. | Pressure analog output / Temperature analog output Current output 4 to 20 mA (maximum load resistance 350Ω or less) (Display value ± 2% of F.S.) | |||
External input | One-point teaching, zero point adjustment input (selectable, initial status: invalid) short-circuit current 1.5 mA or less, input time 20 ms or more | |||
IO-Link | IO-Link specification | Ver 1.1 | ||
Baud rate | E8PC- E8PC- | |||
Data length | PD Size: 6 byte OD Size: 1 byte (M-sequence type: TYPE_2_V) | |||
Minimum cycle time | E8PC- E8PC- | |||
Power supply | Power supply voltage | 10 to 30 VDC (including 10% ripple (p-p)), Class 2 | ||
Power consumption | 1,200 mW or less (When power supply voltage is 30 V, current consumption must be 40 mA or less. When power supply voltage is 10 V, current consumption must be 120 mA or less.) | |||
Protection circuit | Power supply reverse connection protection, output short-circuit protection, and output reverse connection protection | |||
Environment resistance | Ambient temperature range | –20 to 80°C in operation and storage, respectively (no condensation) | ||
Ambient humidity range | –35 to 85%RH in operation and storage, respectively (no condensation) | |||
Vibration resistance (destruction) | 1000 VAC, 50/60 Hz, 1 min. between current-carrying parts and case | |||
Shock resistance (destruction) | 10 to 2000 Hz, double amplitude 1.5 mm, 2 hours in X/Y/Z direction each | |||
Impact (endurance) | 500 m/s2, three times in X/Y/Z direction each | |||
Protective structure | IP67 | |||
Pollution degree | 3 | |||
Altitude | 2,000 m or less | |||
Installation place | Indoor | |||
Material | Wetted part | Pressure port: SUS304L, diaphragm pressure port: Al2O3 (alumina), O-ring: FKM | ||
Other than wetted part | Head: PPSU, display unit: PES, button: PBT, chassis: SUS304L | |||
Weight | Approx.190 g | |||
Accessories |
|
Model | E8PC-YA-A18 | E8PC-YA-A14 | E8PC-YA-A38 | E8PC-YA-C18 | E8PC-YA-C14 |
---|---|---|---|---|---|
Thread | G3/4×R1/8 | G3/4×R1/4 | G3/4×R3/8 | G3/4×NPT1/8 | G3/4×NPT1/4 |
A | 43.3 | 47.1 | 47.6 | 43.3 | 47.1 |
B | 21.1 | ||||
C | 13 | ||||
D | 9.2 | 13 | 13.5 | 9.2 | 13 |
E | 34 | ||||
F | 3.7 | 4.8 | 5 | 3.7 | 4.8 |
G | 17 | 17 | 19 | 17 | 17 |